header
Local cover image
Local cover image
Image from OpenLibrary

Investigation of Stainless-Steel Firefighting Tube Failures and Inconel 600 Thermowell Damages in Oil and Gas Fields/ Jumana Fawzy Gharib ; Supervisors: Prof. Waleed Mohamed Abdel Aziz Khalifa, Dr. Rania Mohamed El-Shorbgy.

By: Contributor(s): Material type: TextTextLanguage: English Summary language: English, Arabic Producer: 2023Description: 79 pages : illustrations ; 30 cm. + CDContent type:
  • text
Media type:
  • Unmediated
Carrier type:
  • volume
Other title:
  • دراسة انهيار أنابيب مكافحة حريق من صلب مقاوم للصدأ وتلف مقاييس حرارية مصنوعة من انكونيل ٦٠٠ مستخدمة فى حقول البترول والغاز [Added title page title]
Subject(s): DDC classification:
  • 628.925
Available additional physical forms:
  • Issues also as CD.
Dissertation note: Thesis (M.Sc.) -Cairo University, 2023. Summary: Two corrosion case studies are investigated in this study. In the first case, stainlesssteel firefighting tubes corroded after 3 months of operation. The investigation revealed low quality of the material and pit propagation by tunneling which is characteristic to Microbiological Influenced Corrosion. In the second case, an Inconel 600 thermowell- used in a sulfur recovery unit- was severely burned leading to the inability to follow the unit operating temperature. It was concluded that the damage is hot corrosion. The root cause of the failure is the harsh conditions of operation. Summary: حالات الانهيار نتيجة التآكل هي أكثر حالات الانهيار شيوعًا التي تحدث في حقول البترول والغاز. في هذه الدراسة تم التحقيق فى حالتي تآكل. تضمنت الدراسة الفحص البصري، والبنية العيانية، والبنية المجهرية، والتركيب الكيميائي. في الحالة الأولى، تآكلت أنابيب مكافحة الحرائق المصنوعة من الفولاذ المقاوم للصدأ بعد ٣ أشهر من التشغيل. كشفـت الدراسة عن انخفاض جودة المادة وانتشار التنقير عن طريق الأنفاق وهي آلية مميزة لانتشار التآكل الميكروبيولوجي وهذا قد يفسر التآكل السريع والتسريب في مجموعة الأنابيب. في الحالة الثانية، تعرض مقياس حراري مصنوع من الانكونل ٦٠٠- مستخدم لقياس درجة حرارة المدخنة لمحرقة حرارية بوحدة استخلاص كبريت- لاحتراق شديد. وهذا التلف غير المتوقع أدى إلى عدم القدرة على متابعة درجة حرارة تشغيل الوحدة. خلصت الدراسة إلى أن التلف تم تحديده على أنه تآكل عالى درجة الحرارة مع آليات عمل الأكسدة والكربنة والكبرتة. أظهر تحليل النتائج أن السبب الجذري لانهيار المقياس الحراري هو ظروف التشغيل القاسية نتيجة الارتفاع المفرط في درجة حرارة الاحتراق خارج حدود تصميم الوحدة.
Tags from this library: No tags from this library for this title. Log in to add tags.
Star ratings
    Average rating: 0.0 (0 votes)

Thesis (M.Sc.) -Cairo University, 2023.

Bibliography: pages 74-79.

Two corrosion case studies are investigated in this study. In the first case, stainlesssteel firefighting tubes corroded after 3 months of operation. The investigation
revealed low quality of the material and pit propagation by tunneling which is
characteristic to Microbiological Influenced Corrosion. In the second case, an
Inconel 600 thermowell- used in a sulfur recovery unit- was severely burned leading
to the inability to follow the unit operating temperature. It was concluded that the
damage is hot corrosion. The root cause of the failure is the harsh conditions of
operation.

حالات الانهيار نتيجة التآكل هي أكثر حالات الانهيار شيوعًا التي تحدث في حقول البترول والغاز. في هذه الدراسة تم التحقيق فى حالتي تآكل. تضمنت الدراسة الفحص البصري، والبنية العيانية، والبنية المجهرية، والتركيب الكيميائي. في الحالة الأولى، تآكلت أنابيب مكافحة الحرائق المصنوعة من الفولاذ المقاوم للصدأ بعد ٣ أشهر من التشغيل. كشفـت الدراسة عن انخفاض جودة المادة وانتشار التنقير عن طريق الأنفاق وهي آلية مميزة لانتشار التآكل الميكروبيولوجي وهذا قد يفسر التآكل السريع والتسريب في مجموعة الأنابيب. في الحالة الثانية، تعرض مقياس حراري مصنوع من الانكونل ٦٠٠- مستخدم لقياس درجة حرارة المدخنة لمحرقة حرارية بوحدة استخلاص كبريت- لاحتراق شديد. وهذا التلف غير المتوقع أدى إلى عدم القدرة على متابعة درجة حرارة تشغيل الوحدة. خلصت الدراسة إلى أن التلف تم تحديده على أنه تآكل عالى درجة الحرارة مع آليات عمل الأكسدة والكربنة والكبرتة. أظهر تحليل النتائج أن السبب الجذري لانهيار المقياس الحراري هو ظروف التشغيل القاسية نتيجة الارتفاع المفرط في درجة حرارة الاحتراق خارج حدود تصميم الوحدة.

Issues also as CD.

Text in English and abstract in Arabic & English.

There are no comments on this title.

to post a comment.

Click on an image to view it in the image viewer

Local cover image