Impact of phase change materials on the performance of the thermally activated buildings / (Record no. 169317)

MARC details
000 -LEADER
fixed length control field 05001namaa22004091i 4500
003 - CONTROL NUMBER IDENTIFIER
control field OSt
005 - أخر تعامل مع التسجيلة
control field 20250223033340.0
008 - FIXED-LENGTH DATA ELEMENTS--GENERAL INFORMATION
fixed length control field 241207s2023 |||a|||f |m|| 000 0 eng d
040 ## - CATALOGING SOURCE
Original cataloguing agency EG-GICUC
Language of cataloging eng
Transcribing agency EG-GICUC
Modifying agency EG-GICUC
Description conventions rda
041 0# - LANGUAGE CODE
Language code of text/sound track or separate title eng
Language code of summary or abstract eng
-- ara
049 ## - Acquisition Source
Acquisition Source Deposit
082 04 - DEWEY DECIMAL CLASSIFICATION NUMBER
Classification number 621
092 ## - LOCALLY ASSIGNED DEWEY CALL NUMBER (OCLC)
Classification number 621
Edition number 21
097 ## - Degree
Degree Ph.D
099 ## - LOCAL FREE-TEXT CALL NUMBER (OCLC)
Local Call Number Cai01.13.11.Ph.D.2023.Mo.I.
100 0# - MAIN ENTRY--PERSONAL NAME
Authority record control number or standard number Mona Ahmed Abdel Mawla Keshk,
Preparation preparation.
245 10 - TITLE STATEMENT
Title Impact of phase change materials on the performance of the thermally activated buildings /
Statement of responsibility, etc. By Mona Ahmed Abdel Mawla Keshk; Under the Supervision of Prof. Dr. Adel Khalil Hassan Khalil
246 15 - VARYING FORM OF TITLE
Title proper/short title تأثير استخدام المواد متغيرة الطور على أداء المباني النشطة حراريا /
264 #0 - PRODUCTION, PUBLICATION, DISTRIBUTION, MANUFACTURE, AND COPYRIGHT NOTICE
Date of production, publication, distribution, manufacture, or copyright notice 2023.
300 ## - PHYSICAL DESCRIPTION
Extent 107 pages :
Other physical details illustrations ;
Dimensions 30 cm. +
Accompanying material CD.
336 ## - CONTENT TYPE
Content type term text
Source rda content
337 ## - MEDIA TYPE
Media type term Unmediated
Source rdamedia
338 ## - CARRIER TYPE
Carrier type term volume
Source rdacarrier
502 ## - DISSERTATION NOTE
Dissertation note Thesis (Ph.D)-Cairo University, 2023.
504 ## - BIBLIOGRAPHY, ETC. NOTE
Bibliography, etc. note Bibliography: pages 99-107.
520 ## - SUMMARY, ETC.
Summary, etc. This study reports the feasibility and performance of thermally activated building systems with <br/>and without Phase Change Materials for the hot and dry climate zone of North Africa. Using a <br/>validated simulation model, four system configurations are examined for different melting <br/>temperatures and thicknesses of the Bio-PCMs. The four PCM-TABS systems are also <br/>compared to two reference systems with an active ceiling or floor. The configurations were <br/>assessed thermally by the PMVand PCH beside that, the energy saving and the energy cost <br/>were considered. Also, other experimental tests were performed on two cuboids to test the <br/>performance of the radiant floor with and without PCM. The results show that the use of PCMs <br/>is feasible for hot and dry climates, with reductions in energy consumption and running energy <br/>costs of up to 18.46 and 19.8 %, respectively, achieved when PCMs are incorporated into the <br/>radiant ceiling while having a melting temperature of 22 °C and thickness of 6 cm, and those <br/>savings increase when using larger volumes of PCMs with melting temperatures closer to the <br/>setpoint temperature. This comes with a slight reduction in the PPD from nearly 100 % in the <br/>reference systems to no less than 95.5%. In contrast, the total costs of the energy and the PCM <br/>together increased with the increase of the PCM’s thickness as the maximum total cost saving <br/>was 9% achieved when PCMs have a melting temperature of 22°C and thickness of 1 cm. Also, <br/>the numerical results proved that the PCM able to reduce temperature fluctuation by up to 35% <br/>compared to the cases without PCM. The best integration scheme to simultaneously decrease <br/>the mean PPD and increase the PCH is a radiant ceiling with a PCM floor for PCM melting <br/>temperature and thickness of 24°C and 5 cm. The experimental results showed that the PCM <br/>could save up to 84.56 % of the chilled water energy.
520 ## - SUMMARY, ETC.
Summary, etc. هذه الدراسة عن أداء المباني النشطة حراريا مع وبدون المواد متغيرة الطور في المناخ الحار والجاف. تم فحص أداء أربعة صور للنظام فيما يتعلق بالمواضع النسبية لألواح المواد متغيرة الطور ودرجة حرارة الانصهار والحجم. تم تقييم النظام حراريًا من خلال نسبة عدم الراحة الحرارية ونسبة ساعات الراحة، مع مراعاة توفير الطاقة والتكلفة. أيضًا، تم إجراء اختبارات تجريبية على مكعبين بحجم 1م3 لاختبار الأرضية المشعة مع وبدون المواد متغيرة الطور. تظهر النتائج أن استخدام المواد المتغيرة الطور مع المباني النشطة حراريا أدى الى انخفاض في استهلاك الطاقة وتكاليفها يصل إلى 18.46 و19.8٪، على التوالي مع انخفاض طفيف في نسبة ساعات الراحة من 100 ٪ إلى مالا يقل عن 95.5 ٪. وتم تحقيق أقصى توفير إجمالي في التكلفة بنسبة 9٪. أظهرت التجارب أن المواد متغيرة الطور يمكن أن توفر حتى 84.54٪ من طاقة تبريد المياه.
530 ## - ADDITIONAL PHYSICAL FORM AVAILABLE NOTE
Issues CD Issued also as CD
546 ## - LANGUAGE NOTE
Text Language Text in English and abstract in Arabic & English.
650 #7 - SUBJECT ADDED ENTRY--TOPICAL TERM
Topical term or geographic name entry element Mechanical Power Engineering
Source of heading or term qrmak
653 #0 - INDEX TERM--UNCONTROLLED
Uncontrolled term Phase change material
-- Radiant cooling
-- Thermally activated building
-- Energy consumption
700 0# - ADDED ENTRY--PERSONAL NAME
Personal name Adel Khalil Hassan Khalil
Relator term thesis advisor.
900 ## - Thesis Information
Grant date 01-01-2023
Supervisory body Adel Khalil Hassan Khalil
Discussion body Mahmoud Abdel Wahab Kassem
-- Mohamed Fatouh Ahmed
Universities Cairo University
Faculties Faculty of Engineering
Department Department of Mechanical Power Engineering
905 ## - Cataloger and Reviser Names
Cataloger Name Nourhan
Reviser Names Huda
942 ## - ADDED ENTRY ELEMENTS (KOHA)
Source of classification or shelving scheme Dewey Decimal Classification
Koha item type Thesis
Edition 21
Suppress in OPAC No
Holdings
Source of classification or shelving scheme Home library Current library Date acquired Inventory number Full call number Barcode Date last seen Effective from Koha item type
Dewey Decimal Classification المكتبة المركزبة الجديدة - جامعة القاهرة قاعة الرسائل الجامعية - الدور الاول 07.12.2024 89367 Cai01.13.11.Ph.D.2023.Mo.I. 01010110089367000 07.12.2024 07.12.2024 Thesis
Cairo University Libraries Portal Implemented & Customized by: Eng. M. Mohamady Contacts: new-lib@cl.cu.edu.eg | cnul@cl.cu.edu.eg
CUCL logo CNUL logo
© All rights reserved — Cairo University Libraries
CUCL logo
Implemented & Customized by: Eng. M. Mohamady Contact: new-lib@cl.cu.edu.eg © All rights reserved — New Central Library
CNUL logo
Implemented & Customized by: Eng. M. Mohamady Contact: cnul@cl.cu.edu.eg © All rights reserved — Cairo National University Library